Page 34 - {COVP2017}
P. 34

Code of Veterinary Practice For Poultry Processing Plant

                              coils and, if applicable, the water used to defrost the coil.

                      6.7.4   On ceiling mounted cooling units, the drain water should
                              be confined by suitable insulated drip trays directly
                              connected to the drainage system.
                      6.7.5   Provision should be made so that during the defrost
                              procedure, air circulating fans on the unit being defrosted
                              can be switched off to prevent carryover of defrost water.

                6.8   Thawing
                      6.8.1   A chiller used for thawing frozen carcass or carton product
                              to allow boning or further processing should be equipped
                              with machinery to maintain a maximum air temperature
                              of 15°C during the entire thawing operation.
                      6.8.2   A recording thermometer should be installed to give a
                              continuous record of the air temperature.

                6.9   Condensation
                      6.9.1   Refrigerated rooms should be designed and operated in
                              a way that prevents the formation and accumulation of
                              condensate on overhead structures and ceilings.

                      6.9.2   Refrigerated departments should not be constructed
                              above other departments unless the lower is to operate
                              at temperature consistently below those of the upper.
                      6.9.3   Main refrigerant lines should not be routed through
                              working areas.
                      6.9.4   Where forced draught unit coolers or air distribution
                              ducting are located in the work area, both the drain trays
                              and ducting should be insulated.

           7.0   FREEZER FACILITIES AND COLD STORES

                7.1   Introduction
                      This section is applicable to freezer and cold store facilities on
                      processing plants. This section refers to the following ‘types’ of
                      freezers and cold stores: